OPERATION: CONFIGURATION MODE

COMMAND LETTERS AND INDEX (Table 3.13)
Command
Command Index
Function
Command Bytes
# Of Characters
Default Value
RW
RW
GPRW
RW
RW
-
RW
GPRW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
GPRW
RW
RW
GPRW
GPRW
GPRW
GPRW
-
GPRW
GPRW
RW
RW
GPRW
RW
RW
RW
RW
RW
RW
01
02
03
04
05
06
07
08
09
0A
0B
0C
0D
0E
0F
10
11
12
13
14
15
16
17
18
19
1A
1B
1C
1D
1E
1F
20
21
22
23
24
25
26
SP1
SP2
RDGOFF
OUTOFF
ID
N/A
INPUT
RDGCNF
AL1CNFG
AL2CNFG
LOOP BREAK TIME
OUT1CNF
OUT2CNF
RAMPTIME
ANGLSCL
COMM.PARAMETERS
RSP1
AL1LO
AL1HI
RDGSCL
AL2LO
AL2HI
PB1/DEAD BAND
RESET 1
RATE 1
CYCLE 1
N/A
PB2/DEAD BAND
CYCLE 2
SOAK TIME
BUS FORMAT
DATA FORMAT
ADDRESS
Transit Time Interval
RSP 2
RSP 3
C.J. OFFSET ADJ.
Recognition Character
3
3
3
2
2
-
1
1
1
1
2
1
1
2
3
1
3
3
3
3
3
3
2
2
2
1
-
2
1
2
1
1
1
2
3
3
3
1
6
6
6
4
4
-
2
2
2
2
4
2
2
4
6
2
6
6
6
6
6
6
4
4
4
2
-
4
2
4
2
2
2
4
6
6
6
2
200000
200000
200000
00000
0000

04
4A
00
00
003B
81
60
0000
9186A0
0D
200000
A003E8
215F90
100001
A003E8
215F90
00C8
00B4
0000
07

00C8
07
0000
14
02
01
0010
20000
20000
20000
2A

Command Index
Command
Function
D
D
D
E
E
E
X
X
X
X
X
U
U
V
Z
01
02
03
01
02
03
01
02
03
04
05
01
03
01
02
DISABLE ALARM 1
DISABLE ALARM 2
STAND BY
ENABLE ALARM 1
ENABLE ALARM 2
DISABLE STAND BY
SEND MAIN READING
SEND PEAK READING
SEND VALLEY READING
SEND READING
SEND READING
SEND ALARM STATUS
SEND SW VERSION
SEND DATA STRING
HARD RESET

Command Format
Description:
INPUT.76543210 means 8 bit positions of the Input Command Data (Operand).
INPUT.10= INPUT.5432= INPUT 7.6=
00 TC 0000 J/392-2/0-10 mV 00=100 ohm RTD
01 RTD 0001 K/392-3/0-1 V 01=500 ohm RTD
10 PC 0010 T/392-4/0-10 V 10=1000 ohm
11 NIA 0011 E/385.2/0-20 mA  
  0101 DIN-J/385.4  
  0110 R  
  0111 S  
  1000 B  
  1001 C  

RDGCNF.210= RDGCNFG.3= RDGCNFG.765=
000 Not Allowed 0 ░C 000 Filter constant 1
001 Decimal Point 1 ░F 001 Filter constant 2
010 Decimal Point 2   10=1000 ohm
011 Decimal Point 3*   010 Filter constant 4
100 Decimal Point 4*   011 Filter constant 8
101   100 Filter constant 16
*Process only   101 Filter constant 32
    110 Filter constant 64
    111 Filter constant 128
Example: To set RTD, 4 wire, .0392 Curve, 100m ohms. The command data is 00001001 Bin = 09HEX. Send *W0705.

AL1CNFG.0= AL1CNFG.1= AL1CNFG.2= AL1CNFG.3=
0 Disable 0 Absolute 0 Unlatch 0 Normally Open
1 Enable 1 Deviation 1 Latch 1 Normally Closed
       
AL1CNFG.54= AL1CNFG.6= AL1CNFG.7=
00 Above 0 Loop Break Alarm Disable 0 Alarm Power On Enable
01 Below 1 Loop Break Alarm Enable 1 Alarm Power On Disable
10 Hi/Lo    
*11 Band    
*Deviation    

AL2CNFG.0= AL1CNFG.1= AL2CNFG.2= AL2CNF3.3=
0 Disable 0 Absolute 0 Unlatch 0 Normally Open
1 Enable 1 Deviation 1 Latch 1 Normally Closed
       
AL2CNFG.54=   AL2CNFG.7=
00 Above   0 Volt Retransmission
01 Below   1 Current Retransmission
10 Hi/Lo    
*11 Band
*Deviation Only

Time Proportional: OUT1CNFG.0= Analog Proportional: OUT1CNFG.0=
0 on/off 0 0-20mA
1 PID 1 4-20mA
OUT1CNFG.1= OUT1CNFG.2= OUT1CNFG.3=
0 Reverse 0 Manual PID 0 Adaptive Enable
1 Direct 1 Auto PID 1 Adaptive Disable
OUT1CNFG.4= OUT1CNFG.5=
0 Anti Wind Up Disable 0 Auto PID Stop
1 Anti Wind Up Enable 1 Auto PID Start

OUT2CN FG.0= OUT2CNFG.1= OUT2CNFG.2=
0 on/off 0 Reverse 0 Manual PID
1 PID 1 Direct 1 Auto PID
OUT2CNFG.3= OUT2CNFG.4= OUT2CNFG.567=
0 Ramp Disable 0 Soak Disable 000 Damping 1
1 Ramp Enable 1 Soak Enable 001 Damping 2
    010 Damping 3
    011 Damping 4
    100 Damping 5
    101 Damping 6
    110 Damping 7
    111 Damping 8

COMM.PARAMETERS.210=   COMM. PARAMETERS.43=  
000 300 BAUD 00 No Parity
001 600 01 odd
010 1200 10 Even
011 2400 11 N/A
100 4800    
101 9600    
110 19200    
COMM. PARAMETERS.5=   COMM. PARAMETERS.6=  
0 7 Bit Data 0 1 Stop Bit
1 8 Bit Data 1 2 Stop Bit

BUSFORMAT.0 = BUS FORMAT.1 = BUSFORMAT.2 =
N/A 0 No LF 0 No Echo
1 LF 1 Echo
BUSFORMAT.3 = BUSFORMAT.4 = BUSFORMAT.5 =
0 RS232 0 Continues 0 CR
1 RS 485 1 Command 1 Space

DATAFORMAT is used for V01 command or continues mode (RS232)
DATAFORMAT .0 = DATAFORMAT .1 = DATAFORMAT .2 =
0 No Status 0 No Reading 0 No Peak
1 Alarm Status 1 Reading 1 Peak
DATAFORMAT .3 = DATAFORMAT .6 = DATAFORMAT .7 =
0 No Valley 0 No Unit N/A
1 Valley 1 Unit  
ADDRESS is applicable for RS485 and can be 01 to 199
TRANSMIT TIME INTERVAL is applicable in RS232 and continues mode which specifies the time between transmission and the minimum time is 500 msec.

RDGOFF.0~19 = RDGOFF.20~22 = RDGOFF.23 =
offset data DP+2 0 positive offset
    1 negative offset
RDGSC.0~18 = RDGSC.19 = RDGSC.20~23 =
scale data 0 direct scale DP+1
  1 reverse scale  

Example: to have an input of 4 to 20mA displayed as 0 to 100,
Scale=(100-0)/(9999-2000)
RDGSC.0~18=1E858
RDGSC.19 = 0 (direct scale)
RDGSC.20~23 = 8(DP=7)
Offset = 0-(0.125) (2000)
RDGOFF.0~19=0019
RDGOFF.20~22=2(DP=0)
RDGOFF.23 = 1, (Offset is negative)
1 negative offset
Send the command as *W03A00019 (offset = A00019) and *W1481E858 (scale = 81E858)
NOTE: To communicate when the continues mode is enabled, the continues mode must be stopped by sending 13 Hex (Xof) and then send ^AE